SELF PRESSURE DIFFENTIAL CONTROL VALVE ENZYC
A. SELF PRESSURE DIFFENTIAL CONTROL VALVE PRODUCT CHARACTERISTICS AND USEGE
ENZYC Self Pressure Diffential Control Valve is such a valve as using the self pressure variation to do self control while keep the pressure differential of the medium flowing through this controlled system unchanged. Suitable for the pressure differential control of the warming supply using a dual-pipeline system to guarantee the system basically unchanged, lower the noise, balance the resistance and get rid of the heat-net and hydraulic imbalance.
B. SELF PRESSURE DIFFENTIAL CONTROL VALVE INSTALLATION DRAWING


ENZYC Adjustable pressure differential
C. SELF PRESSURE DIFFENTIAL CONTROL VALVE MAIN TECHNICAL PARAMETERS
| Model | PN(MPa) | Casing test pressure | Control range of pressure differential | |
| Fixed pressure differential type | Adjustable pressure differential type | |||
| ZYC-16 | 1.6 | 2.4 MPa | 10KPa、20KPa、30KPa | 10~30KPa |
D. SELF PRESSURE DIFFENTIAL CONTROL VALVE MAIN EXTERNAL AND CONNECTING DIMENSIONS
| DN mm |
Way of connection | L mm |
D | D1 | D2 | H(mm) | Flow (m3/h) |
Medium used | Medium temperature | Part material | |
| Fixed pressure differential type | Adjustable pressure differential type | ||||||||||
| 15 | Thread | 110 | 95 | 65 | 45 | 95 | 145 | 0.2-1 | Water | 0~100℃ | Body, upper and lower bonnets: cast iron valve core: copper membrane: nylon reinforced rubber spring: stainless steel |
| 20 | 110 | 105 | 75 | 55 | 110 | 150 | 0.3- 1.5 |
||||
| 25 | 115 | 115 | 85 | 65 | 130 | 165 | 0.5-2 | ||||
| 32 | Flange | 130 | 135 | 100 | 78 | 140 | 190 | 1-4 | |||
| 40 | 200 | 145 | 110 | 85 | 190 | 340 | 1.5-6 | ||||
| 50 | 215 | 160 | 125 | 100 | 205 | 355 | 2-8 | ||||
| 65 | 230 | 180 | 145 | 120 | 240 | 390 | 3-12 | ||||
| 80 | 275 | 195 | 160 | 135 | 300 | 500 | 5-20 | ||||
| 100 | 290 | 215 | 180 | 155 | 350 | 550 | 10-30 | ||||
| 125 | 310 | 245 | 210 | 185 | 380 | 580 | 15-45 | ||||
E. SELF PRESSURE DIFFENTIAL CONTROL VALVE SCHEMATIC DIAGRAM OF INSTALLATION

The technical data subject to amend without notice