Valve Seriers - Water Power Control Valves Seriers
SLOW-CLOSING CHECK VALVE EN300X
A. SLOW-CLOSING CHECK VALVE Structure and Purpose
Used on the pump outlet of a water supply system to prevent medium's back-flow, water hammer and water shock. It has three functions as an electric valve, check valve and water hammer remover. It is capable of improving the safety and reliability of the water supply system effectively through integrating the technical principle of slow-open, speed valve, slow-close, and removing water hammer and preventing of both pump-starting and pump-stopping water hammer. The gate can carry out open-close automatically upon the operation rules of the water pump just by operating the pump to open or close electrically. EN300X Slow-Closing Check Valves features by the big flow and small pressure loss, reliable sealing performance, easy installation, debugging and maintenance and long duration.
B. SLOW-CLOSING CHECK VALVE Brief Figure of Structure




1. Needle Valve 2. Check Valve 3. Small Ball Valve
< DN 450 Diaphragm type valve
< DN 450 Diaphragm type valve
1. Strainer 2. Ball Valve 3. Check Valve 4. Needle Valve
= DN 500 piston type valve
= DN 500 piston type valve
C. SLOW-CLOSING CHECK VALVE Schematic Diagram of Installation

D. SSLOW-CLOSING CHECK VALVE External and Connection Dimensions
| DN(mm) | 20 | 25 | 32 | 40 | 50 | 65 | 80 | 100 | 125 | 150 | 200 | 250 | 300 | 350 | 400 | 450 | 500 | 600 | 700 | 800 | |
| L | 180 | 180 | 180 | 203 | 203 | 235 | 285 | 360 | 400 | 455 | 585 | 650 | 800 | 860 | 915 | 980 | 1075 | 1230 | 1300 | 1450 | |
| PN10 | D | 105 | 115 | 135 | 145 | 160 | 180 | 195 | 215 | 245 | 280 | 335 | 390 | 440 | 500 | 565 | 615 | 670 | 780 | 895 | 1010 |
| D1 | 75 | 85 | 100 | 110 | 125 | 145 | 160 | 180 | 210 | 240 | 295 | 350 | 400 | 460 | 515 | 565 | 620 | 725 | 840 | 950 | |
| PN16 | D | 105 | 115 | 135 | 145 | 160 | 180 | 195 | 215 | 245 | 280 | 335 | 405 | 460 | 520 | 580 | 640 | 705 | 840 | 910 | 1020 |
| D1 | 75 | 85 | 100 | 110 | 125 | 145 | 160 | 180 | 210 | 240 | 295 | 355 | 410 | 470 | 525 | 585 | 650 | 770 | 840 | 950 | |
| PN25 | D | 105 | 110 | 135 | 145 | 160 | 180 | 195 | 230 | 270 | 300 | 360 | 425 | 485 | 550 | 610 | 660 | 730 | 840 | 955 | 1070 |
| D1 | 75 | 85 | 100 | 110 | 125 | 145 | 160 | 190 | 220 | 250 | 310 | 370 | 430 | 490 | 550 | 600 | 660 | 770 | 875 | 990 | |
| H | 172 | 172 | 172 | 265 | 265 | 310 | 350 | 460 | 520 | 570 | 695 | 780 | 905 | 1025 | 1080 | 1030 | 1135 | 1270 | 1460 | 1640 | |
| H1 | 106 | 106 | 106 | 210 | 210 | 215 | 245 | 305 | 365 | 415 | 510 | 560 | 658 | 696 | 735 | 610 | 665 | 725 | 865 | 925 | |
Note: Either elastic seat ring sealed gate valve or butterfly valve can be selected in the schematic of installation. Recommend to select the butterfly valves in case of =DN350
E. SLOW-CLOSING CHECK VALVE Main Technical Features
| Nominal Pressure | 1.0MPa | 1.6MPa | 2.5MPa |
| Shell test pressure | 1.5MPa | 2.4MPa | 3.75MPa |
| Sealed test pressure | 1.1MPa | 1.76MPa | 2.75MPa |
| Suitable temperature | ≤80℃ | ||
| Suitable medium | water | ||
The technical data subject to amend without notice